Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Are the support spacing requirements the same for RTRC conduit as they are for rigid PVC conduit?

0
10 Posted

Are the support spacing requirements the same for RTRC conduit as they are for rigid PVC conduit?

0
10

Although RTRC has a much higher flexural strength than other Rigid Nonmetallic Conduits (RNC) such as PVC, the current NEC® spacing requirements specified in Table 352.30(B), are the same for both materials. However, the CEC® recognizes this material difference and therefore specifies longer distances for RTRC (rule 12-1216) than for rigid PVC (rule 12-1114). 14.