Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Are the conductors within a cable in a LINKOSITY™ power system derated?

0
10 Posted

Are the conductors within a cable in a LINKOSITY™ power system derated?

0
10

A. The connecting components are derated. When they are applied as Type TC/ER or MTW cable the four current carrying conductors of each three phase multi-wire branch circuit are derated from the 90 degree column of NEC® Tables 31015(B)(2)(a) and 310.16 to 80% of identified capacity. When they are applied as “cord” the ampacity is determined per NEC® Tables 400.5 and 400.5A to 80% of identified capacity. In both cases a 20 amp branch circuit is loaded to no more than 80% of capacity, or 16 amps – which is within the allowable derated range of operation for the 12 and 10 AWG conductors.