Are pass-through refrigerators allowed from the ISO 7 clean/buffer room directly into the unclassified pharmacy? Or do they need to pass through to the ante-room only?
Pass-through refrigerators are allowed and should be installed in a manner that will have no negative impact on the environmental controls. 119. Does the anteroom and segregated compounding area need to have the same finishes as the buffer rooms? Since this is cleaned on the same rotation as the buffer room it would seem so, but please clarify. Yes, the ante area and segregated compounding area need to have the same finishes as the buffer area. 120. Where is the best location for the low air return in a negative pressure chemo mixing room in relation to the hood to cause the least disruption of air and assure that the chemo hood will vent correctly? Ideally, air is exhausted and not returned back into a negative-pressure hazardous drug buffer area. Total airflow volume will dictate exhaust volume rate. In some cases, all exhaust air is pulled from the PEC. 121. We have seen some pharmacies that requested that the walls to be coved to each other vertically as well as the walls coved to