Are all of the wires connected to the gas valve properly?
c. Is the venting system functioning? Check for spillage at the diverter. d. Is the gas inlet pressure proper? Read instructions for minimum pressure. 2. This floor furnace cannot be expected to function properly if exposed to wind as found when installed in a house supported by pillars (open foundation). The wind is most harmful if it can go beneath the front of the draft diverter and produces a pressure directly on the outlet of the chamber. This wind can result in pilot outage and a reduction of millivolts, causing the valve not to open. 3. Good operation of this system is dependent on the pilot and generator working properly. It is possible for the pilot to require cleaning yearly. Replace the pilot orifice if cleaning does not produce proper flame. Replacement on the generator alone is not recommended.