Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Are air compressors required to be UL Listed or FM Approved?

air compressors Approved FM UL
0
Posted

Are air compressors required to be UL Listed or FM Approved?

0

No, compressors are not required to be listed/approved. They only need to have enough capacity (hp) to replace the operating air pressure in dry-pipe and double interlock preaction systems within 30 minutes. However, the device used to automatically regulate the air pressure in a sprinkler system must be listed/approved. Hence, a pressure maintenance device must be used. The pressure switch on an automatic air compressor does not qualify as an appropriate means of automatically regulating air pressure in sprinkler system piping.