After installing VisuaLCN, no circuits are showing up in the Network Overview Window. How is this remedied?
Start the Configuration component and go to Server Settings page, make sure the Number of Communication Devices and Highest Module Address for each of them are correct. Configuration example: if you have two communication ports and COM2 is attached to the network adapter then set the Communication Devices to 2. Set the Highest Module Address of COM1 to 0 then the Highest Module Address of COM2 should be set to 8 if the module addresses are 1 through 8. Once Everything has been correctly entered restart Server then Client.