How do I test the Phoenix Triple IR Flame Detector?
Net Safety has developed a test lamp specifically for the Phoenix Triple IR to be tested while in a hazardous location. Simply point the lamp at the Phoenix Triple IR and initiate test sequence. The Phoenix Triple IR is also designed with an Automatic Visual Integrity (VI) feature which tests the detector’s optical surface every three minutes (that is, unless a momentary background IR condition is detected in which case the VI timer resets). The Phoenix Triple IR can also be tested while in a non-hazardous area using a real fire. Consult the User Manual for further testing information.